Operation Of The Cooling Water System

Aug 10, 2020

Leave a message

Regarding the environmental conditions of a running industrial chiller, the load has become a fixed value. At this time, the condensing heat load is also a fixed value. It is stipulated that the temperature difference between the inlet and outlet water is 5℃, the cooling water volume must also be a certain value and the flow rate is inversely proportional to the temperature difference between the inlet and outlet water. Therefore, the operation of the chiller. As long as the temperature difference between the inlet and outlet of the cooling water is specified, this flow is usually controlled by the pressure drop of the cooling water in and out of the condenser. Under standard working conditions, the pressure drop of the condenser inlet and outlet water is set to 68.6 kPa (0, 7kg/cm:).

In the actual operation of the cooling water system, there are often the following misoperations:

1. Failure to close the inlet valve of the condenser on the unit that does not need to be opened before starting the machine, causing water leakage. A part of the cooling return water flows away from the condenser of the unit that is not started, reducing the flow of cooling water in the condenser of the running unit, causing the condensing pressure to rise. The operating current of the host increases. The cooling capacity of the unit decreases. Stop running. It wastes electricity, reduces the cooling effect, and easily damages the equipment.

2. Due to the previous misoperation, the condensing pressure of the host and the temperature of the cooling water outlet increased. Cause misjudgment to operators. It is mistaken that the condenser inlet valve and the cooling water pump outlet valve are opened large because the cooling water is not enough, and some even add cooling tower fans, which causes the power consumption of water pumps and cooling tower fans to increase

3. What's more, blindly open a cooling water pump. Although adding the cooling water pump can indeed reduce the cooling water temperature and condensing pressure, after all, the electrical energy of a water pump is wasted. Therefore, the correct operation method of the cooling water system is:

(1) Before starting the machine, close the condenser water inlet valve of the unit that does not need to be operated to prevent water leakage.

(2) Open the inlet and outlet valves on the condenser of the unit to be operated (generally, the outlet valve is normally open, and the inlet valve is opened and closed as required. The condenser and evaporator are the same). Turn on the corresponding cooling water pump. Adjust the condenser inlet and outlet water The pressure drops to about 68.6kPa (0.7 kg/cm:) (the pressure drop is based on the principle that it can overcome the resistance of the pipeline. A lower value is better for energy saving).

(3) If the pointer of the condenser water inlet and outlet pressure gauge swings too much, it indicates that there is air in the cooling water system. The air needs to be exhausted and the pressure gauge indicates normal to continue the next operation.

The high-pressure liquid refrigerant of industrial water chillers flows out through the filter and enters the evaporator through capillary throttling and pressure reduction. Due to the decrease in pressure, the refrigerant continuously absorbs the heat transferred from the air to the evaporator in the evaporator and evaporates into vapor. The vapor is then compressed The machine inhales, passes through the body, and then passes through the oscilloscope to the capillary tube. This cycle continues to move the indoor heat out of the outdoor and reduce the indoor temperature.